Product Code: KEWSMARTPAT
In Stock
The SMARTPAT Wi-Fi controlled PAT tester stands out as the fastest PAT solution available.
This innovative tester is the world’s first Wi-Fi-enabled PAT tester, allowing for remote control via the free KEWPAT App on your smartphone or tablet. This feature streamlines the testing process, enabling users to conduct tests more efficiently and with greater ease.
In addition to its remote control capabilities, the SMARTPAT offers a comprehensive range of testing functions, ensuring that all necessary checks are performed swiftly and accurately. Its user-friendly interface and advanced features make it a top choice for professionals seeking to enhance their PAT testing procedures.
As well as covering all your basic requirements for Portable Appliance Testing, the SMARTPAT hosts a number of advanced features that mean you can be sure you have a PAT to test any appliance. The SMARTPAT has an added benefit of being able to conduct a run leakage test at 230V and 110V, a unique feature in the battery powered market to Kewtech. There is also an advanced function to perform 10mA and 30mA Portable RCD tests.
Provides a very fast solution for logging your testing. Special drop down menus on the APP ensures quick appliance documentation enabling you to add basic information such as appliance and location, or more detailied logging such as make, model, serial number and special comments.
The APP controls the tester so you can use the standard auto-tests or make up your own. The test results are automatically included in the appliance record.
All appliances need a risk assessment. The APP has a risk assessment function that is designed to be optionally engaged during each test if required, leading to the desired frequency of re-test.
Class 1 equipment has a variable pass limit depending on the length of the mains lead. There is a simple cable calculator on the APP that can be easily engaged during testing.
The APP makes full use of your mobile device as it can take pictures, scan barcodes / QR codes and can also give you voice prompts.
The SMARTPAT in conjunction with the KEWPAT APP and the SimplyPats Manual+ software is the ultimate in PAT testing. It gives you control over your testing sequences, you can collect as much data as you need, including risk assessment, and provides an easy-to-use, yet sophisticated PC based product register. Modern technology making testing faster, easier and more robust
The SMARTPAT, together with the KEWPAT APP, covers all the functionality and more of a traditional downloading PAT tester.
The KEWPAT app, in conjunction with KEWTECH testers, changes the face of PAT testing by removing all the data logging leg work and allowing you to be more efficient with your testing. KEWPAT can be operated manually with any Kewtech PAT tester enabling fast manual documentation including appliance risk assessment, record documentation and covers your obligations for holding a product register.
The app has a large data storage for high volume testing to meet all your PAT testing needs. You can take a picture and add it to the product register, scan a barcode, and add your own logo to printed labels all in a matter of seconds. You can even produce a professional PDF report ready for email or print through the app. Alongside the SMARTPAT you can see the true power of the markets most efficient testing solution. By running the tester from the KEWPAT app you will have your results sent straight back to your app in a matter of seconds!
The KEWPAT app can also operate the KEW80L Bluetooth Printer which instantly prints your PASS/FAIL labels with a number of different designs to choose from, including barcodes and QR codes. Simply scan the QR or barcode label and the app will auto-populate with the appliance previously collected data for even faster testing on your return visits.
If you are looking for greater flexibility in managing your PAT testing data and want access to large number of PAT Test Reporting and Invoicing options, then SimplyPats Version 7 (Downloading Edition) can already import and export data to and from the KEWPAT App.
| ELII0PAT KIT | 110v appliance adapter kit |
| ELKIT | ELII0PAT kit plus 230v & 400v 16A adapters |
| EZYMAIN 110V | 110v supply lead for the EZYPAT Plus and SMARTPAT |
| KEWSNAP 1 | 50 Snap tags with clips |
| KEWSNAP 2 | 50 Snap tags without clips for cable tie fixing |
| KEWPRINT | Bluetooth label printer |
| KEWROLL | 460 Labels for Kewprint |
| LR EARTH | Long reach 65mm earth probe |
| PATLOG 1 | A4 PAT testing log book / product register |
| PATLOG 3 | A5 PAT testing log book / product register |
| 250FAIL | 250 appliance fail labels |
| 500PASS | 500 appliance pass labels |
| 500VIS | 500 appliance visual pass labels |
| KEWPAT APP | Free Download from kewtechcorp.com |
| Protective Conductor Resistance Test | ||
| Measuring range | 0.00 - 20.00 Ω (NULL value inc)* | |
| Over-range indication | > 20.00 Ω | |
| Resolution | 0.01Ω | |
| Open-circuit voltage | 5 V ±0.4 V DC | |
| Measuring current | 200 mA DC (nominal value) | |
| Accuracy | ±3%rdg ±5dgt | |
| Mains Voltage | ||
| Display Range | 30 - 270 V | |
| Hi/Lo Indication | < 30 V: No voltage indication; > 270 V: 270 V | |
| Resolution & Accuracy | 1 V & ±3%rdg ±5dgt | |
| Insulation | ||
| Rated Voltage | 250v | 500v |
| Measuring Range | 0.00 - 20.00 MΩ | |
| Over-range Indication | > 20.00 MΩ | |
| Resolution | 0.01 MΩ | |
| No-load Voltage | 250 V DC +20%, -0% | 500 V DC +20%, -0% |
| Short-circuit Current | 1.5 mA DC or less | |
| Rated Current | 1 -1.2 mA with a load of 0.25 MΩ | 1 to 1.2 mA with a load of 0.5 MΩ |
| Accuracy | ±2%rdg±3dgt | |
| Sustitute Leakage | ||
| Measuring range | 0.10 - 12.00 mA rms | |
| Over-range indication | > 12.00 mA | |
| Resolution | 0.01mA | |
| Open-circuit voltage/ Freq | 30 V ±5 V rms / 50 Hz ±5% | |
| Measuring current | 1.2 mA AC ±0.5 mA (when measuring 12.00 mA) | |
| Accuracy | ±3%rdg±5dgt | |
| Insulation Test Between L & N | ||
| Open-circuit voltage | 4.5 V ±0.5 V DC | |
| Criteria of judgement | 100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ” and the measurement is halted. | |
| Run Leakage (Item: Load current / Leakage current) EZYPAT Plus and SMARTPAT ONLY | ||
| Mains voltage range | 100 - 253 V / 50 Hz | |
| Measuring range | 0.10 - 13.00 A rms 0.10 - 20.00 mA rms | |
| Display range | 0.00 - 13.00 A 0.00 - 20.00 mA | |
| Over-range indication | > 13.00 A > 20.00 mA | |
| Resolution | 0.01A / 0.01mA | |
| Accuracy | ±10%rdg ±5dgt / ±3%rdg ±5dvgt | |
| Max. rating | 3 kVA max., 15 sec. cont. / - | |
| RCD Test SMARTPAT ONLY | ||
| Rated voltage | 230 V - 15% to +10% / 50Hz | |
| Rated current | 10 mA / 30 mA | |
| Test duration | ×1: 0.0 ms - 500.0 ms / ×5: 0.0 ms - 40.0 ms | |
| Test current accuracy | 2% - 8% | |
| Operating time accuracy | ±2 ms ( 40 ms) ±8 ms (>40 ms) | |
| UK Mainland | Order by 2pm for Next Day Delivery* |
|---|---|
| Under £25.00 | £4.50 |
| Over £25.00 | FREE |
| UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
|---|---|
| Under £80.00 | £15.00 |
| Over £80.00 | FREE |